Siemens SENTRON PAC4200 Manual page 167

Power monitoring device
Hide thumbs Also See for SENTRON PAC4200:
Table of Contents

Advertisement

Appendix
A.2 Modbus
Offset
Number of
Name
registers
6199
6
Minimum phase angle L1-L1
6205
6
Minimum phase angle L1-L2
6211
6
Minimum phase angle L1-L3
6217
6
Minimum Line Frequency with Time
6223
6
Minimum 3-Phase Average Voltage L-N with
Time
6229
6
Minimum 3-Phase Average Voltage L-L with
Time
6235
6
Minimum 3-Phase Average Current L-L with
Time
6241
6
Minimum Total Apparent Power with Time
6247
6
Minimum Total Active Power with Time
6253
6
Minimum Total Reactive Power (Qn) with
Time
6259
6
Minimum Total Power Factor (Qn) with Time Float + time stamp
6265
6
Minimum Neutral Current with Time
6271
6
Minimum Total Reactive Power (Qtot) with
Time
6277
6
Minimum Total Reactive Power (Q1) with
Time
6283
6
Min. Sliding Window Demand Voltage L1-N
with Time
6289
6
Min. Sliding Window Demand Voltage L2-N
with Time
6295
6
Min. Sliding Window Demand Voltage L3-N
with Time
6301
6
Min. Sliding Window Demand Voltage L1-L2
with Time
6307
6
Min. Sliding Window Demand Voltage L2-L3
with Time
6313
6
Min. Sliding Window Demand Voltage L3-L1
with Time
6319
6
Min. Sliding Window Demand Current L1
with Time
6325
6
Min. Sliding Window Demand Current L2
with Time
6331
6
Min. Sliding Window Demand Current L3
with Time
6337
6
Min. Sliding Window Demand Apparent
Power L1 with Time
6343
6
Min. Sliding Window Demand Apparent
Power L2 with Time
6349
6
Min. Sliding Window Demand Apparent
Power L3 with Time
6355
6
Min. Sliding Window Demand Active Power
L1 with Time
166
Format
Unit
Float + time stamp
°
Float + time stamp
°
Float + time stamp
°
Float + time stamp
-
Float + time stamp
V
Float + time stamp
V
Float + time stamp
A
Float + time stamp
VA
Float + time stamp
W
Float + time stamp
VAR
-
Float + time stamp
A
Float + time stamp
VAR
Float + time stamp
VAR
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
V
Float + time stamp
A
Float + time stamp
A
Float + time stamp
A
Float + time stamp
VA
Float + time stamp
VA
Float + time stamp
VA
Float + time stamp
W
System Manual, 05/2019, A5E02316180B-05
Value
Access
range
-
R
-
R
-
R
45 ... 65 R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
-
R
PAC4200