Technical data
9.1 Technical data
Measuring inputs for voltage
Table 9- 1
Device with wide-voltage power supply
Voltage L-N
Voltage L-L
Table 9- 2
Device with extra-low voltage power supply
Voltage L-N
Voltage L-L
Table 9- 3
Values for devices with a wide-voltage power supply and devices with an extra-low voltage power supply
Min. measurable
Voltage L-N
voltage
Voltage L-L
Impulse withstand voltage
Measuring category
Input resistance (L-N)
Power consumption per phase
Measuring inputs for current
Only for connection to AC power systems via external current transformers
Input current I
Rated current 1
Rated current 2
Measuring range
Measuring range
Surge withstand capability
Max. permissible continuous current
Power consumption per phase
Zero point suppression
The measuring range is the range within which the accuracy data applies
1)
128
AC 3~ 400 V (+20%), max. 347 V for UL
AC 3~ 690 V (+20%), max. 600 V for UL
AC 3~ 289 V (+20%)
AC 3~ 500 V (+20%)
I
for current
1)
for power
1)
Measuring category CAT III
Measuring category CAT III
Measuring category CAT III
Measuring category CAT III
AC 3~ 57 V -80%
AC 3~ 100 V 80%
> 9.5 kV (1.2/50 μs)
Acc. to IEC/UL 61010 Part 1
1.05 Mohms
Max. 220 mW
AC 3~ x/1 A
AC 3~ x/5 A
10% to 120% of rated current
1 % to 120 % of rated current
100 A for 1 s
10 A
4 mVA at 1 A
115 mVA at 5 A
0 to 10% of rated current
System Manual, 05/2019, A5E02316180B-05