Outdoor Air Temperature Sensor - FULTON Endura EDR-750 Installation And Operation Manual

Condensing hydronic boilers 750,000 - 2,000,000 btu/hr
Hide thumbs Also See for Endura EDR-750:
Table of Contents

Advertisement

OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
3-24
Sensor. Refer to Figure 63 for factory default settings:
ƒ
P gain: The gain applied for the Proportional portion of the PID equation.
I gain: The gain applied for the Integral portion of the PID equation.
ƒ
D gain: The gain applied for the Derivative portion of the PID equation.
ƒ
FIGURE 62 - SENSOR CONFIGURATION
FIGURE 63 - CENTRAL HEAT CONFIGURATION MODULATION
ƒ Outdoor Air Temperature Sensor
The outdoor reset temperature sensor is to be configured on the master boiler
only or a standalone boiler. Starting from the status screen tap configure and
then scroll to and select sensor configuration. The outdoor temperature source
needs to be assigned to EnviraCOM outdoor sensor. Ensure values are as
indicated in Figure 64.
Once the outdoor temperature source has been established the outdoor reset
option must be enabled. For a lead/lag boiler plant this must be done through
the lead lag master configuration. Return to the configuration screen and scroll
to and select lead lag master configuration. Select the box in the bottom right
SECTION 3
EDR-IOM-2019-0212
© Fulton Group N.A., Inc. 2019