SECTION 3
EDR-IOM-2019-0212
FIGURE 64 - OUTDOOR AIR SENSOR CONFIGURATION
hand corner labeled advanced settings. Using the left and right arrow keys scroll
to the screen labeld outdoor reset. Once at the outdoor reset configuration
screen select the enable option in the row labeled "enable". Refer to Figure 65 for
factory default settings:
FIGURE 65 - OUTDOOR RESET CONFIGURATIONS
For a standalone boiler application the outdoor reset must be configured
through a different screen. To access this screen start from the boiler status
screen select configuration and scroll to and select outdoor reset configuration.
Follow similar steps as above.
To access the outdoor reset curve select the box labeled show line in the bottom
right hand corner of the outdoor reset configuration screen. The factory default
curve is displayed in Figure 66. There will be two separate curves. The green curve
corresponding to the normal setpoint and the red curve corresponding to the
time of day setpoint. Both curves are a liner interpolation between the minimum
and maximum outdoor temperatures and the normal and time of day setpoints.
The setpoints can be configured through the lead lag master configuration
screen for a lead lag boiler plant or through the central heat setpoint screen
for a standalone boiler. The low water temperature and the minimum and
maximum outdoor temperatures can be configured through the outdoor reset
configuration screen displayed in Figure 65.
To enable warm weather shutdown for a lead lag boiler plant start from the
boiler status screen and select configure. Scroll to and select lead lag master
Questions? Please Contact Your Local Manufacturer's Representative
OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
3-25