Central Heat Configuration - Modulation Screen; Changing High Limit Setpoint And Verifying Change - FULTON Endura EDR-750 Installation And Operation Manual

Condensing hydronic boilers 750,000 - 2,000,000 btu/hr
Hide thumbs Also See for Endura EDR-750:
Table of Contents

Advertisement

SECTION 3
EDR-IOM-2019-0212
the previous Setpoint screen to the Modulation Screen (Figure 36). This screen
provides access to the PID (Proportional, Integral and Derivative) of the control.
The sola password is also required to change these parameters.
FIGURE 36 - CENTRAL HEAT CONFIGURATION - MODULATION SCREEN
ƒ Changing High Limit Setpoint and Verifying Change
From the Status Summary Screen press Configure, then High Limits; this screen
will be used to set and/or test the Outlet High Limit Setpoint (Figure 37). The
sola password must be entered. By touching the Setpoint next to Outlet High
Limit Setpoint you can adjust the temperature up and down for the Setpoint you
desire or lower it for testing purposes. This change will require Verification. Verify
as follows:
FIGURE 37 - HIGH LIMITS SCREEN
1. Arrow back to the Configuration Menu and press Verify down in the lower
right hand corner. Figure 38.
Questions? Please Contact Your Local Manufacturer's Representative
OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.