FULTON Endura EDR-750 Installation And Operation Manual page 68

Condensing hydronic boilers 750,000 - 2,000,000 btu/hr
Hide thumbs Also See for Endura EDR-750:
Table of Contents

Advertisement

OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
3-20
From the Lead Lag Master Configuration screen select the box labeled Advanced
Settings in the bottom right hand corner. Use the left and right arrows to scroll
to the screen labeled modulation. The row labeled modulation backup sensor
needs to be set to lead outlet sensor. Refer to Figure 55 for factory default
settings:
Off Hysteresis: The differential above setpoint when the boiler is turned off.
ƒ
On Hysteresis: The differential from setpoint when the lead boiler is turned
ƒ
on.
P gain: The gain applied for the Proportional portion of the PID equation.
ƒ
I gain: The gain applied for the Integral portion of the PID equation.
ƒ
D gain: The gain applied for the Derivative portion of the PID equation.
ƒ
From the Lead Lag Master Configuration screen Select the box labeled Advanced
Settings in the bottom right hand corner. Use the left and right arrows to scroll to
the screen labeled Algorithms. The two rows labeled lead selection method and
Lag selection method need to be set to measured run time. Refer to Figure 56 for
factory default settings:
EDR-IOM-2019-0212
FIGURE 55 - MODULATION
FIGURE 56 - ALGORITHMS
SECTION 3
© Fulton Group N.A., Inc. 2019