To Wire An Equipment Touch To The Vav Zone Ii - Carrier VAV Zone II Installation And Startup Manual

Table of Contents

Advertisement

Installing the VAV Zone II
LED
The blue LED on the top of the Wireless Adapter indicates the following:
If the LED is...
Off
Blinking
Steadily on

To wire an Equipment Touch to the VAV Zone II

NOTES
The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
If the Equipment Touch will be:
Daisy-chained on the Rnet with ZS sensors or a Wireless Adapter, use the standard 4-conductor Rnet
wiring and follow the wiring instructions To wire ZS sensors to the VAV Zone II (page 17).
The only device on the Rnet, you can use a 2-conductor cable instead of the standard 4-conductor Rnet
cable and follow the instructions below.
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
CAUTION The VAV Zone II can share a power supply with the Carrier controller as long as:
The power supply is AC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
Turn off the VAV Zone II's power.
1
Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
2
Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
3
Wire the VAV Zone II's Rnet+ and Rnet- terminals to the terminals of the same name on the Equipment
4
Touch's connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
VAV Zone II Controllers
Installation and Start-up Guide
Then the device...
Is not powered or there is a problem.
Is working properly.
Has a problem. Do one of the following:
Cycle power to the device.
Insert a small screwdriver or paper clip into the hole next to the LED to reboot the
device.
20
CARRIER CORPORATION ©2019
All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents