Installing the VAV Zone II
LED
The blue LED on the top of the Wireless Adapter indicates the following:
If the LED is...
Off
Blinking
Steadily on
To wire an Equipment Touch to the VAV Zone II
NOTES
The Equipment Touch requires a 24 Vac power supply. It is not powered by the Rnet.
If the Equipment Touch will be:
Daisy-chained on the Rnet with ZS sensors or a Wireless Adapter, use the standard 4-conductor Rnet
○
wiring and follow the wiring instructions To wire ZS sensors to the VAV Zone II (page 17).
The only device on the Rnet, you can use a 2-conductor cable instead of the standard 4-conductor Rnet
○
cable and follow the instructions below.
For complete Equipment Touch installation instructions including wiring diagrams, see the Equipment Touch
Installation and Setup Guide.
CAUTION The VAV Zone II can share a power supply with the Carrier controller as long as:
The power supply is AC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
Turn off the VAV Zone II's power.
1
Partially cut, then bend and pull off the outer jacket of the cable. Do not nick the inner insulation.
2
Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
3
Wire the VAV Zone II's Rnet+ and Rnet- terminals to the terminals of the same name on the Equipment
4
Touch's connector.
NOTE If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
VAV Zone II Controllers
Installation and Start-up Guide
Then the device...
Is not powered or there is a problem.
Is working properly.
Has a problem. Do one of the following:
Cycle power to the device.
Insert a small screwdriver or paper clip into the hole next to the LED to reboot the
device.
20
CARRIER CORPORATION ©2019