Appendix C: Zs Sensor Display For Vav Zone Ii - Carrier VAV Zone II Installation And Startup Manual

Table of Contents

Advertisement

Appendix C: ZS Sensor display for VAV Zone II

Appendix C: ZS Sensor display for VAV Zone II
Property
Active Alarms
Active Maintenance
Active Air Source Linkage
Mode
Supply Air Temp
Air Flow Percentage of
Nominal
Outdoor Air Temperature
1
Rnet text is the scrolling text that appears on the ZS Pro Sensor's display.
NOTES
To view properties on the Diagnostic Screen, hold the
information to help troubleshoot your system.
The Rnet tag is displayed on the ZS sensor display.
To view properties on the Info Screen, press the
VAV Zone II Controllers
Installation and Start-up Guide
ZS Screen
Rnet Tag
Diagnostic
1550
Diagnostic
1551
Diagnostic
1552
Info
304
Info
308
Info
button. Tap the button to cycle through information.
100
Description
Rnet Text
1
-nonE
No Active Alarms
StP-AL
Zone Temp Alarm
SPco2-AL
Zone CO2 Alarm
SP_rH-AL
Zone Humidity Alarm
Sat-AL
Supply Air Temp Alarm
-nonE-
No Active Maintenance
SnSr-FLt
Sensor Fault
Fltr-dtY
Dirty Filter
Llnc-FLt
Linkage Fault
OFF
Off
hEAt-uP
Warm-up
hEAt
Heat
cooL
Cool
FrEEcool
Freecool
PrESSrZE
Pressurize
EuAcuATE
Evacuate
vEnt
Vent
no-Llnc
Linkage Not Active
Air Source Supply Air
Temp, if available
% of design air flow
Outside Air Temp
button for 3 seconds. Tap the button to cycle through
CARRIER CORPORATION ©2019
All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents