Turn on the VAV Zone II's power.
5
Turn on the Equipment Touch.
6
To wire the TruVu™ ET Display
WARNING Do not apply line voltage (main) - 24 Vdc power only.
Wiring power
Wire the TruVu™ ET Display 24V DC connector to the 24 Vdc power supply using 2-conductor 18 AWG wire.
Maximum distance 100 feet (30 meters).
CAUTION The TruVu™ ET Display can share a power supply with the Carrier controller as long as:
The power supply is DC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
Wiring communication
Turn off the VAV Zone II's power.
1