Output resolution
Integral airflow sensor
Battery
Protection
BT485 connector
Status indicators
Environmental operating
range
Storage temperature range
Physical
Controller and actuator
overall dimensions
Controller and actuator
mounting dimensions
Controller overall
dimensions
Controller mounting
dimensions
Actuator overall dimensions
Actuator mounting
dimensions
Panel depth
Shaft dimensions
VAV Zone II Controllers
Installation and Start-up Guide
8 bit D/A
Precision differential pressure sensor 0–2 in. H2O, sensitive down to ±0.001 in.
H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) I.D. tubing.
Allows for readings across the 0–2 in. H2O range, accurate to ±5% of full flow at 2
in. H2O.
10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, editable properties,
schedules, and trends.
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
CAUTION To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
You attach a BT485 (not included) to a controller at the beginning and end of a
network segment to add bias and to terminate a network segment.
LEDs indicate status of communications, running, errors, power, and digital
outputs
32 to 130°F (0 to 54.4°C), 10–90% relative humidity, non-condensing
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
UL94-5VA plenum rated enclosure for installation in plenum (or other space for
environmental air) in accordance with NEC Section 300.22 (c) and (d)
Width:
8.9 in. (22.7 cm)
Height:
5.9 in. (15.0 cm)
7.1 in. (18.0 cm) from left side controller mounting hole centerline to actuator
mounting hole centerline
Width:
6.4 in. (16.3 cm)
Height:
5.7 in. (14.5 cm)
Depth:
2.1 in. (5.3 cm)
5.3 in. (13.4 cm) from left side controller mounting hole centerline to right side
controller mounting hole centerline
Width:
3.0 in. (7.6 cm)
Height:
5.9 in. (15.0 cm)
Depth:
2.5 in. (6.4 cm)
4.4 in. (11.2 cm) from shaft centerline to actuator mounting hole centerline
2.5 in. (6.4 cm) minimum
Minimum shaft diameter: .25 in. (.64 cm)
Maximum shaft diameter: .63 in. (1.59 cm)
Minimum shaft length: 1.75 in. (4.45 cm)
5
Introduction
CARRIER CORPORATION ©2019