Zone Temp - Configure additional ZS or wireless temperature sensors used on the VAV
Zone II.
Use - Check to include ZS or wireless sensors' value in the Combined Algorithm
(Average is the default).
Raw Value - Displays sensed temperature for each ZS or wireless temperature
sensor's address
Calibration - If needed, enter value to adjust the Corrected Value from the Raw
Value, in order to calibrate an individual ZS or wireless sensor's sensed value.
Combination Algorithm - Use Average, Maximum, or Minimum zone temperature to
calculate the Corrected Value for temperature control.
Zone Humidity - Configure additional ZS or wireless humidity sensors used on the VAV
Zone II.
Use - Check to include ZS or wireless sensors' value in the Combined Algorithm
(Maximum is the default).
Raw Value - Displays sensed humidity for each ZS or wireless humidity sensor's
address
Calibration - If needed, enter value to adjust the Corrected Value from the Raw
Value, in order to calibrate an individual ZS or wireless sensor's sensed value.
Combination Algorithm - Use Average, Maximum, or Minimum ZS or wireless
humidity to calculate the Corrected Value for humidity control.
VAV Zone II Controllers
Installation and Start-up Guide
Appendix A: VAV Zone II Points/Properties
87
D:
(Index) Area - (1) Main
Sensor
Use - checked
Calibration - 0
Combination Algorithm -
Average
Input Smoothing - None
Show on Sensors -
Calculated Value
Display Resolution - 1
COV Increment - .1
D:
(Index) Area - (1) Main
Sensor
Use - unchecked
Calibration - 0
Combination Algorithm -
Maximum
Input Smoothing - None
Show on Sensors -
Calculated Value
Display Resolution - 1
COV Increment - 1