Point Name/Description
Supply Air Temperature – Displays the current supply air temperature.
Supply Air Temp Calibration – A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
Space Relative Humidity – Displays the current value of relative humidity sensor, if
present.
Relative Humidity Calibration – You can enter a calibration offset for the relative
humidity. The offset is added to or subtracted from the controller's RH input value, and
the calculated value is shown in the Status > Space Relative Humidity.

Setpoints

Navigation:
i-Vu® / Field Assistant:
Select a color band on the setpoint graph to see the current setpoints in the Heating and Cooling fields. The values in this
graphic are Fahrenheit. See setpoint descriptions below.
NOTE This graphic is an example only. Your setpoints may differ.
VAV Zone II Controllers
Installation and Start-up Guide
Properties
Control Program
>
73
Appendix A: VAV Zone II Points/Properties
Default/Range
R:
-56 to 245°F
(-48.9 to 118.3°C)
D:
0 °F/ °C
R:
-9.9 to 10 °F
(-5.5 to 5.5 °C)
R:
0 to 100%
D:
0%
R:
-15 to 15%rh
Configuration
Setpoints
>
>