Carrier VAV Zone II Installation And Startup Manual page 106

Table of Contents

Advertisement

Appendix D: BACnet points list for the VAV Zone II Fan Terminal
Point Name
Occupied Cooling Setpoint
Reset Filter Alarm
Setpoint Adjustment
Shutdown
VAV Reheat
Air Source Mode
BAS On / Off
Optimal Start Type
Space Temp Source
Terminal Mode
Terminal Type
Zone Type
Airside Linkage Status
Filter
High SPT
Indoor Air Quality
Low SPT
VAV Zone II Controllers
Installation and Start-up Guide
Point
Units
Access
R/W
°F
R/W
0=Off
1=On
R/W
0=Disable
1=Enable
0=Inactive
R/W
1=Active
R/W
0=Disable
1=Enable
R
1=OFF
2=WARM-UP
3=HEAT
4=COOL
5=FREECOOL
6=PRESSURIZE
7=EVACUATE
8=VENT
1=Inactive
R/W
2=Occupied
3=Unoccupied
R/W
1=None
2=Temp Compensated
3=Learning Adaptive
R
1=Sensor Failure
2=SPT Sensor
3=T55 / T56
4=Network
5=Airside Linkage
6=Locked Value
7=ZS Sensor
8=Wireless Sensor
1=Off
R
2=Heating
3=Warm-Up
4=Vent
5=N/A
6=Cooling
7=Dehumidify
8=Reheat
9=Pressurize
10=Evacuate
11=Shutdown
12=IAQ Override
13=Air Balancing
R
1=Single Duct
2=Parallel Fan
3=Series Fan
1=Slave
R
2=VVT Master
3=VAV Master
R
0=Normal
1=Alarm
R
0=Clean
1=Dirty
0=Normal
R
1=Alarm
R
0=Normal
1=Alarm
R
0=Normal
102
Default
BACnet Point Name
Value
75
occ_cl_stpt
Inactive (0)
filter_rntm_clr
Active (1)
stpt_adj_enable
Active (1)
shutdown
Active (1)
vav_reheat
link_ahu_mode
1
keypad_ovrde
2
start_type
spt_status
terminal_status
terminal_type
zone_type
air_linkage_fail
filter_alarm
spt_hi_alarm
iaq_alarm
spt_lo_alarm
CARRIER CORPORATION ©2019
BACnet
BACnet Object
ID
AV:3001
BV:7517
BV:1013
BV:9001
BV:1029
MSV:2005
MSV:1001
MSV:2009
MSV:2003
MSV:2006
MSV:2007
MSV:2008
BV:7030
BV:7017
BV:7011
BV:7005
BV:7012
All rights reserved