Addressing The Vav Zone Ii; Wiring For Communications - Carrier VAV Zone II Installation And Startup Manual

Table of Contents

Advertisement

Apply power to the power supply.
5
Measure the voltage at the VAV Zone II's power input terminals to verify that the voltage is within the
6
operating range of 21.6–26.4 Vac.
Connect a 4-inch (10.2 cm) wire from Gnd to the control panel.
7
Insert the screw terminal connector into the VAV Zone II's power terminals.
8
Verify that the Power LED is on and the Run LED is blinking.
9

Addressing the VAV Zone II

You must give the VAV Zone II an address that is unique on the network. You can address the VAV Zone II before
or after you wire it for power.
If the VAV Zone II has been wired for power, pull the screw terminal connector from the controller's power
1
terminals labeled Gnd and 24 Vac. The controller reads the address each time you apply power to it.
Using the rotary switches, set the controller's address. Set the Tens (10's) switch to the tens digit of the
2
address, and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller's address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
0
CAUTION The factory default setting is 00 and must be changed to successfully install your VAV Zone II.

Wiring for communications

The VAV Zone II communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.
VAV Zone II Controllers
Installation and Start-up Guide
1's
0
15
Installing the VAV Zone II
CARRIER CORPORATION ©2019
All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents