Addressing The Vvt Bypass Ii; Wiring For Communications; Wiring Specifications For Bacnet Ms/Tp And Arc156 - Carrier VVT Bypass II Installation And Startup Manual

Table of Contents

Advertisement

Installing the VVT Bypass II

Addressing the VVT Bypass II

You must give the VVT Bypass II an address that is unique on the network. You can address the VVT Bypass II
before or after you wire it for power.
1
If the VVT Bypass II has been wired for power, pull the screw terminal connector from the controller's power
terminals labeled Gnd and 24 Vac. The controller reads the address each time you apply power to it.
2
Using the rotary switches, set the controller's address. Set the Tens (10's) switch to the tens digit of the
address, and set the Ones (1's) switch to the ones digit.
EXAMPLE If the controller's address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
0
CAUTION The factory default setting is 00 and must be changed to successfully install your VVT Bypass
II.

Wiring for communications

The VVT Bypass II communicates using BACnet on the following types of network segments:
MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
ARC156 communicating at 156 kbps
NOTE For more networking details, see the Open Controller Network Wiring Installation Guide.

Wiring specifications for BACnet MS/TP and ARC156

Cable:
Maximum length:
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
VVT Bypass II Controller
Installation and Start-up Guide
1's
0
22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
2000 feet (610 meters)
14
CARRIER CORPORATION ©2019
All rights reserved

Advertisement

Table of Contents
loading

Table of Contents