Chapter 7 – Commissioning

7.1 Introduction

This chapter explains several tasks that may be required during commissioning.
First time switch-on and Commissioning should only be carried out by a Honeywell engineer or someone with
System Administrator privileges who has been trained in accordance with this manual.
During First Time Switch On, it will be necessary to confirm or set the Date, Time and Language, to set new
passwords and delete the default password.
If the system was ordered from Honeywell Analytics, complete the section
Modules' and 'Channel Configuration for input channels' before proceeding with 'Channel Configuration for
the Relay Output channels'.

7.2 First Time Switch On

Before switching power on, ensure that a qualified person has checked that the wiring is safe and conforms to
local regulations, and that all electrical connections are in accordance with Section 4. Also check that the
battery switches are 'On'. (If a backup battery is fitted)
Switch on the battery switch (if fitted) and apply power. You can use a multi-meter to check that the DC supply
to the DC Connector block is between 18 and 32 VDC. (≥24 VDC when a battery is installed.)
The system start up sequence may last for up to 5 minutes depending on the number of channels in use.
When start up is completed, Touchpoint Plus will display the Input screen, indicating the current status of the
system. The Channel list view with Inhibits is shown below:
Key to Icons:
Commissioning
Toggle to select screen layout
External main power is provided.
Touch for status
External power is not connected.
Touch for status
Event History (Inhibit shown)
Login Status (Viewer)
Toggle auto-scroll on and off
Online monitoring
Login Status(Admin)
Login Status(Engineer)
Login Status(Operator)
SD card is detected
Menu
Filter Display (Inhibits shown)
Wind direction
51
Touchpoint Plus Wireless
Technical Handbook
'Commission Input / Output

Advertisement

Table of Contents
loading

Table of Contents