3020M5001_Iss 1_07/18
Chapter 16 – Fault Codes
Code
Display in Event History
1
Communication fault [B/D Type], Pos: xx, Code: xxx
2
Memory fault [B/D Type], Pos: xx, Code: xxx
3
Catalogue memory fault
4
Internal hardware fault [B/D Type], Pos: xx, Code: xxx
5
Sensor circuit fault CH: xx, [B/D Type], Pos: xx, Code: xxx
6
Supplied voltage fault [B/D Type], Pos: xx, Code: xxx
7
Internal software fault [B/D Type], Pos: xx, Code: xxx
8
9
Sensor fault CH: xx, [B/D Type], Pos: xx, Code: xx
10
mA Output Error CH: xx, [B/D Type], Pos: xx
11
Relay Output Error CH: xx, [B/D Type], Pos: xx
12
Detector In Fault CH: xx, [B/D Type], Pos: xx
13
Battery Fault Pos: xx
IO B/D Not Matched [B/D Type], Pos: xx,
14
Prev: xxx, Current: xxx
15
Negative Reading CH: xx, [B/D Type], Pos: xx, Conc: xxxx
16
Fault Cleared CH: xx, [B/D Type], Pos: xx, Code: xx
17
Reset all faults
Fault Codes
91
Touchpoint Plus Wireless
Description
Internal communication fault
internal memory fault
Catalogue memory corrupted
Internal hardware fault
Sensor circuit fault
Supplied voltage fault
Internal software failure
Reserved
Sensor fault (including signal range fault)
Reserved
Relay not controlled
Remote fault notified by a detector
(depending on fault signal range)
Backup battery fault
IO board not matched or present
Cell is producing a negative reading
(depending on gas under-range limit)
Fault self-cleared
Manually reset all faults