3020M5001_Iss 1_07/18
3.1.2 Weights
System with packaging
Note: One input module, one relays, one WIO module, AC power and backup battery based for basic
3.1.3 Dimensions
3.1.4 Ambient Operating Temperature
–10 °C to +55 °C (14 °F to 131 °F)
3.1.5 Overall Ambient Operating Humidity
5 % to 95 %RH, non-condensing
3.1.6 Storage Conditions (Without batteries)
–25 °C to +60 °C (-13 °F to 140 °F), @ 5 % to 95 %RH, non-condensing
3.1.7 Storage Conditions (With batteries)
1 year:
3 months:
1 month:
3.1.8 IP Rating
The system and expansion unit are sealed to IP65 when appropriate cable entry glands are used.
3.1.9 Construction
The system cabinets are constructed from PC ABS plastic with a secured quick release front access door
panel.
The Controller door panel holds a touch sensitive colour LCD with a membrane cover over additional buttons,
LEDs and an audible warning horn.
Inside the Controller cabinet is a Switched-Mode Power Supply (SMPS) providing a nominal DC 24 V output,
an optional Lithium-ion backup battery, a Main Module, a mA/mV Input Module, one Relay
Modules, protection fuses, and the control and user interface electronics.
The optional expansion unit (available end of 2015) holds the same modules and optional backup battery, but
has no controller or user interface.
Both cabinets contain a common Earth (ground) rail that must be bonded to Protective Earth (Ground) through
an isolation switch that does not disconnect the Earth line.
System General Description
System alone
Table 3.
External Dimension
Depth
Length
Width
Table 4.
–20 °C to +25 °C (–4 °F to +077 °F)
–20 °C to +45 °C (–4 °F to +113 °F)
–20 °C to +60 °C (–4 °F to +140 °F)
TPPL basic unit
8.5 Kg (18.7 lbs)
9 Kg (20 lbs)
System Weights
Millimetres
156
426
300
System Dimensions
16
Touchpoint Plus Wireless
Technical Handbook
Remark
Inches
6.2
16.9
11.8