Output Electrical Specifications; System Electrical Specifications - Huawei UPS5000-A-30 kVA User Manual

Hide thumbs Also See for UPS5000-A-30 kVA:
Table of Contents

Advertisement

UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual

8.8 Output Electrical Specifications

Item
Output system
Voltage
Frequency
Total harmonic
distortion of
output voltage
(THDv)
Output PF
Transfer time
Output voltage
unbalance
Overload
capability

8.9 System Electrical Specifications

Item
Parallel system
reliability
Parallel system ECO
Issue 11 (2018-12-10)
In monitoring and power versions earlier than V100R002C01SPC007, the battery voltage is 360–480 V
DC (30 to 40 batteries, 32 by default).
30 kVA
Three-phase, four-wire, and PE wire
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
In normal mode, the mains frequency is synchronized with the bypass
input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance ± 0.05%).
≤ 1% (full linear load)
≤ 4% (full non-linear load)
1
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
± 3%
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Load > 150% or a short circuit occurs: run for 200 ms
30 kVA
Parallel signals use redundancy design.
Supported
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
40 kVA
40 kVA
80 kVA
80 kVA
181