4.3.2.2 Communications Settings

Figure 4-33 Comm. Config. page

4.3.2.3 Control

You can control the system running status on the Control page.
Issue 11 (2018-12-10)
Description
each battery string have the same
charge voltage and discharge
voltage. When a value exceeds
the specified range, an alarm is
generated.
The calculation formula is
(Charge/Discharge voltage –
Average voltage)/Average
voltage x 100%.
After this function is enabled, an
alarm is generated if the
configured battery capacity
exceeds the charging capacity of
the rack.
In battery mode, the UPS can
automatically power off
according to the preset shutdown
delay time. If the parameter is
disabled, this function is not
available.
An alarm is generated if this
parameter is set to Enable and
the backup time is less than the
warning threshold.
An alarm is generated if this
parameter is set to Enable and
the remaining capacity is less
than the warning threshold.
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
20
10–30
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
Disable
Disable, Enable
132