Figure 4-38 Site configuration
Issue 11 (2018-12-10)
The NTP parameters are used to set the NTP server address, port number, and
synchronization interval.
The default SNMP version is SNMPv3, and the preset MD5/SHA password is
Changeme1, and the preset DES/AES password is Changeme2. Change the password
after your first login, preventing unauthorized access.
To obtain the MIB file, choose Config. > Site Config. > SNMP > Download
HUAWEI_UPS_MIB.
The SNMP Trap is used to set the IP address of a server on which the NMS software is
installed. The trap port needs to be the same as that on the NMS. If SNMP Trap is
incorrectly set or not set, system information will be lost or not reported in time.
The certificate is used for Secure Sockets Layer (SSL) encryption protection for WebUI
login. You need to apply to a third-party institution for the certificate.
Configuration Management is used to upload and export configuration parameters in
the monitoring system.
Multi-brand Management is used to import the brand information of a partner to the
corresponding WebUI.
Specify Email server IP address, Sender's email, and User account authentication
required when sending a mail and click Test to check whether the test email can be
received. Configure Alarm Notification Server is used to configure a server for
receiving alarm emails from the monitoring system.
Set Email and Alarm Severity and simulate an alarm. Check that the alarm email can be
received. Configure Alarm Notification Email Address is used to configure the email
address for receiving alarm emails from the monitoring system.
ModbusTCP Certificate Management: ModbusTCP supports the Transport Layer
Security (TLS) secure protocol for encrypted transmission and implements access
Copyright © Huawei Technologies Co., Ltd.