Huawei UPS5000-A-30 kVA User Manual page 136

Hide thumbs Also See for UPS5000-A-30 kVA:
Table of Contents

Advertisement

UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
Item
D.G. mode
D.G. power
limiting (kVA)
D.G. charger
power ratio (%)
Input cur.
limiting
Input cur.
limiting ratio
(%)
Output Setting
Item
Zero display
with no load
output
Output
interruption
transfer time
(ms)
Max. BPM
transfer times
Issue 11 (2018-12-10)
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Set these two parameters to
control the valid input current
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Specifies whether to enable or
disable input current limiting to
protect generators.
Limits the input current to protect
the D.G.
Description
If this parameter is set to Enable,
the output current is displayed as
0 when no load is output. The
output load rate is displayed as
3%. When this parameter is set to
Disable, the output current and
output load rate are not adjusted
to zero.
The interruption for the UPS to
transfer from normal mode to
bypass mode is 1–2 ms, and from
bypass mode to normal mode is
0–20 ms. Set this parameter
based on the output interruption
time acceptable to loads.
Cross currents occur during the
transfer between bypass mode
and normal mode, which impacts
the system. This parameter
specifies the number of transfers
between bypass mode and
normal mode within 1 hour,
which ensures system security.
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
Disable
Disable, Enable
Depends on the
0 kVA to 5000
actual model.
kVA
0
0%–100%
Disable
Disable, Enable
200%
50%–200%
Default Value
Value Range
Enable
Disable, Enable
0
0 ms, 40 ms, 60
ms, 80 ms, 100
ms, 120 ms
5
1–10
127