Control - Huawei UPS5000-A-30 kVA User Manual

Hide thumbs Also See for UPS5000-A-30 kVA:
Table of Contents

Advertisement

UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
Item
GEN
OL
STA
OUT
MT
BP/SYSMT
BP/SYSMT switch function
Settings Wizard
When the UPS starts for the first time or restarts after restoring factory settings, the settings
wizard automatically starts.
After first startup, set basic parameters, including the language, date and time, network
parameters, and common parameters.
Restore Default Settings Screen
Restore default settings after the inverter shuts down.

4.2.5 Control

On the Main Menu screen, select Control and press
Control screen is displayed. The preset password is 000001. After you enter the password,
press
Issue 11 (2018-12-10)
Default settings can be successfully restored only after you set DIP1, DIP2, and DIP3 on the DIP switch
to ON, ON, and OFF respectively.
. The Control screen is displayed.
Copyright © Huawei Technologies Co., Ltd.
Description
Enable or disable D.G. connection detection.
Enable or disable BCB connection detection.
Enable or disable battery circuit breaker status
detection.
Enable or disable PDC output circuit breaker status
detection.
Enable or disable PDC maintenance circuit breaker
status detection.
If the BP/SYSMT switch is set to Enable, the port has
dry contact signal access. Using the port depends on
the status of the BP/SYSMT switch.
If the BP/SYSMT switch is set to Enable, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is used to
detect the status of the PDU bypass input switch, or
system maintenance switch.
. The login screen for accessing the
4 LCD and WebUI
120