Huawei UPS5000-A-30 kVA User Manual page 34

Hide thumbs Also See for UPS5000-A-30 kVA:
Table of Contents

Advertisement

UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
Silk Screen
BCB_STA
BCB_0V
BCB_DRV
SWITCH STATUS_OUT Monitors the UPS output
SWITCH STATUS_0V
SWITCH STATUS_MT
SWITCH STATUS_0V
SWITCH STATUS_BP
SWITCH STATUS_0V
EPO_12V
EPO_NO
Issue 11 (2018-12-10)
NO is short for normally open, and NC is short for normally closed.
When the dry contact signal cable of an external device connects to UPS dry contacts, ensure that
the silk screen names of the dry contacts at both ends of the cable match with each other.
Copyright © Huawei Technologies Co., Ltd.
Description
Monitors the battery circuit
breaker.
Port for signal ground
Controls the trip of the
battery switch in the BCB
box.
circuit breaker on the output
power distribution cabinet
(PDC).
Port for signal ground
Monitors the maintenance
circuit breaker on the output
PDC.
Port for signal ground
Monitors the bypass input
circuit breaker on the input
PDC.
Port for signal ground
12 V power supply
Triggers EPO.
2 Overview
Status
Status:
Closed: battery circuit
breaker ON
Open: battery circuit
breaker OFF
The initial status is Open.
N/A
Voltage:
0 V: battery switch not
tripped
12 V: battery switch
tripped
The initial port voltage is 0 V.
Status:
Open: circuit breaker OFF
Closed: circuit breaker ON
The initial status is Closed.
N/A
Status:
Open: circuit breaker ON
Closed: circuit breaker
OFF
The initial status is Open.
N/A
Status:
Open: circuit breaker OFF
Closed: circuit breaker ON
The initial status is Closed.
N/A
N/A
The initial status is Open.
EPO is triggered if the dry
contact is closed.
25