UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
Batt. sharing affects the actual discharge current and the estimated discharge time.
Incorrect settings will cause a high or low charge current, which tends to damage batteries.
An incorrect estimated discharge time may cause a data backup failure.
When Single/Parallel is set to Single, the Batt. sharing parameter is unavailable.
Retain default values for the Cur. Limit coef. and Cell float volt. parameters. Only
professional maintenance personnel can change the values.
Figure 4-18 Battery Settings Screen
Item
Single batt.
volt.
Single batt.
cap.
Issue 11 (2018-12-10)
Basic Parameters
Figure 4-19 Basic Parameters screen
Description
Specifies the voltage of each
battery that is connected in the
battery string in series.
Specifies the capacity of each
battery that is connected in the
battery string in series.
Copyright © Huawei Technologies Co., Ltd.
4 LCD and WebUI
Default Value
Value Range
12 V
2, 6, 12
Depends on the
5–9999
actual model.