UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
Figure 3-34 Installing the L-shaped brackets
Step 6 Adjust the cabinet position so that the expansion bolt holes are aligned with the four holes at
the bottom of the cabinet.
Step 7 Check the cabinet levelness using a level. If the cabinet is not leveled, adjust the leveling feet.
Step 8 Secure the two L-shaped brackets to the ground using four M12x60 expansion bolts, as shown
in
Step 9 Install a lock for the maintenance bypass switch, as shown in
----End
Rack-mounting the UPS
Step 1 Install guide rails at the bottom of the rack. The guide rail is 2 U high. The methods for
installing guide rails on the left and right sides are the same.
Install the UPS5000-A-80 kVA at the bottom of the rack because it uses bottom cable routing
and weighs more than 160 kg.
1.
Issue 11 (2018-12-10)
Figure
3-34.
The rack must comply with IEC 297. The rack depth is greater than or equal to 1100 mm.
The distance between mounting bars on the same side must be greater than 820 mm.
Reserve sufficient clearance in the lower part of the rack for bottom cable routing.
Level the bottom plane of a guide rail with the bottom line of the U scale 01, and engage
the mounting brackets on both ends of the guide rail into the mounting holes of the
mounting bar, as shown in
Copyright © Huawei Technologies Co., Ltd.
Figure
3-35.
3 Installation
Figure
3-30.
63