UPS5000-A-30 kVA & 40 kVA & 80 kVA
User Manual
Item
Altitude
Noise

8.4 Safety Regulations and EMC

Item
Safety regulations
EMC

8.5 Mains Input Electrical Specifications

Item
Input system
Rated input voltage
Input voltage
Issue 11 (2018-12-10)
30 kVA
0–1000 m
When the altitude is above 1000 m (maximum 4000 m), see
IEC62040-3 to check how the load power is derated.
At 25° C and atmospheric pressure:
100% load: 58 dB (30/40 kVA); 63 dB (80 kVA)
30 kVA
EN62040-1: 2013
IEC62040-1: 2013
YD/T1095-2010
EN62040-2
IEC62040-2
IEC61000-3-11
IEC61000-3-12
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
EN61000-4-6
IEC61000-4-8
30 kVA
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
80–280 V AC (phase voltage)
At 30–40° C: The UPS works at full load when the voltage is
187–280 V AC and is derated to 40% load when the voltage
is 187–80 V AC.
At 0–30° C: The UPS works at full load when the voltage is
176–280 V AC and is derated to 40% load when the voltage
is 176–80 V AC.
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
40 kVA
40 kVA
40 kVA
80 kVA
80 kVA
80 kVA