HDL KNX / EIB
4.2.10 Objects "Scene"
NO.
Object name
Output N
20
This communication object is used to control the scene. The scene control see following
explain:
Telegram value:
e.g:
Hexadecimal
00h------call scene 1 (If scene allocated)
01h------call scene 2 (If scene allocated)
3Fh------call scene 64 (If scene allocated)
80h------store scene 1 (If scene allocated)
81h------store scene 2 (If scene allocated)
BFh------store scene 64 (If scene allocated)
Table 14 Scene(8bits)
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
Function
Scene(8bit)
C R N N N N N N
C: 0-Call scene
1-Store scene(If scene allocated and the scene is the
R: Reserved
N: Scene NO.(bin:000000...111111=NO.1...64)
Switch Actuators
Flags
C W U
current switch state)
www.hdlchina.com
Data type
EIS14
DPT 18.001
1byte
46/58