HDL M/R4.16.1 Manual page 34

Knx/eib bus
Table of Contents

Advertisement

HDL KNX / EIB
---Blinds UP('0'-value)
---Blinds DOWN('1'-value)
---Adjustment time
---Delay time for running direction changed
---Moving time(2..65535s):
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
The blinds function need combination two channels work together.
the first channel control UP/Adjust/Stop of Blind and the second
channel control DOWN/Adjust/Stop of blinds. It runs by receiving
telegram value '0'/'1' from the bus and stop when timeout or receiving
adjustment object telegram value.
The first channel for blinds UP or adjustment.
Options: channel "N"(N=current channel)
This channel output control blinds UP or adjustment.
It's can select another channel as second channel for blinds DOWN
Options: channel "M"(M= another channels )
e.g. If first channel is "channel A" and the maximum channel number
is 4 of the device, can only select channel B or channel C or channel
D for second channel
Control mode
Options: Move UP/DOWN and Adjustment
Move UP/DOWN
Move UP/DOWN and Adjustment: This selection can control the
blinds UP or DOWN,can adjust the blinds,too.
Move UP/DOWN: This selection can only control the blinds UP or
DOWN
This parameter set blinds adjustment time.
seconds,Minimum time is 50ms
When running direction changed,Delay for
seconds,Minimum time is 50ms
This parameter set blinds moving need to take total time.
Options:0.. 65535s
Switch Actuators
maximum time 5
The
maximum time 5
inertia. The
www.hdlchina.com
34/58