HDL M/R4.16.1 Manual page 24

Knx/eib bus
Table of Contents

Advertisement

HDL KNX / EIB
---Change staircase lighting time via bus
---Alarm staircase lighting to bus
---Time for off:(0...255 Min)
---Time for off:(0...59 Sec)
---Warning staircase lighting(ON->OFF->ON)
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
Control staircase light with three mode.
Options:Start with '1', Stop with '0'
Start with '1', Invalid with '0'
Start with '1'/'0' , Can't Stop
Start with '1', Stop with '0': when received telegram value is '1',The
staircase light start and switching ON.when received telegram value
is '0' or time out,switching OFF and stop staircase light.
Start with '1', Invalid with '0': when received telegram value is
'1',The staircase light start and switching ON.Invalid with telegram
value '0'.
Start with '1'/'0' , Can't Stop: when received telegram value is
'1'or'0',The staircase light start and switching ON
Options: NO
YES
NO: Can't change staircase lighting delay off time via bus , only
can be set by ets.
YES:Allow change staircase lighting delay off time via bus by user.
Options: NO
YES
NO: Not Alarm.
YES: Alarm staircase light.
Duration minutes of the staircase lighting delay off time.
Duration seconds of the staircase lighting delay off time.
Options: NO
YES
NO: Not allow alarm
YES: Allow alarm.
Switch Actuators
www.hdlchina.com
24/58