HDL KNX / EIB
>>:--Alarm telegram number(1..255,0-unlimited)
---PWM cycle time set (1...65535) min
---PWM cycle time set (0...59) sec
---Control telegram is received as
---transmit status response object "telegram: status heating"
---"ON" position of valve
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
This parameter is set ON counter overflow alarm interval.
Options: 1..255s
This parameter set the ON counter overflow alarm number.
Options:0-unlimited
1..255
Options:1...65535m
This cycle time is set Minimum is 1 minutes
Options:0..59s
This cycle time is set in seconds
Type of control can be control as 1bit or 1byte.
Options: 1bit PWM(1-start/0-stop)
1byte(255-switch ON/0-switch OFF/ other valve)
1bit PWM(1-start/0-stop): The PWM start and switch ON by the
value of receiving telegram "1" , and stop by "0".
1byte(255-ON/0-OFF/other valve): the switch ON always by the
value of receiving telegram "255", the switch OFF by the value of
receiving telegram "0". The PWM runs and pulse width of PWM is set
according to the value of receiving telegram (1 to 254 )
It has three option for the channel state response setting
Options: No response
Always response
Only after changed
No response: no response switch state.
Always response: always response switch state of the channel when
receive the channel telegram data.
Only after changed: only response switch state of the channel when
change state changed.
Switch Actuators
www.hdlchina.com
40/58