Configuring The System Manually - Siemens FC361 Series Technical Manual

Fire control panel
Hide thumbs Also See for FC361 Series:
Table of Contents

Advertisement

10.4.2 Configuring the system manually

A6V10421795_en--_k
Some devices are assigned to corresponding device types automatically (see
chapter Appendix E: Device type list [➙ 138]).
Create default control logics as per pre-definition.
NOTICE
Before configuring the system manually, make sure that the panel is in normal
operation.
To modify using 'FC360 Panel Configurator'
1. Connect PC to the panel. See chapter 'Connecting a PC to the panel [➙ 107]'.
2. Open a web browser.
3. Enter web address with 'fc360.siemens.com' and press <Enter>.
 'FC360 Panel Configurator' is open.
4. Enter access level 3 password to log into access level 3.
5. Modify configuration as needed.
 Generally the following configuration may be modified in 'FC360 Panel
Configurator':
Customer texts
Properties and parameter settings
Allocation of devices and zones
Control logics
6. After finishing modification, click 'Apply'.
 A confirmation window is open.
7. Click 'OK' to download the modified configuration to the panel. (The panel is at
access level 3.)
 The panel restarts automatically.
 The configuration finishes.
Commissioning
General commissioning steps
10
111 | 151

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc362 seriesFc361-zzFc361-zaFc362-zzFc362-za

Table of Contents