Indicators; Reset Buttons; S100 Reset Periphery Board; S1201 Reset Core 'A' Detector Circuit - Siemens FC2025 Manual

Fire alarm control panel marine application
Table of Contents

Advertisement

FS20 Marine Fire Detection Control Panel

Indicators

12.7
Standard LED indicators
LED
Color
H1301
Yellow
H1701
Yellow

Reset Buttons

12.8

12.8.1 S100 RESET Periphery Board

Button
Function
S100
Reset main microprocessor on
periphery board

12.8.2 S1201 RESET Core 'A' Detector Circuit

Button
Function
S1201
Reset main microprocessor for
core A detector circuit

12.8.3 S1601 RESET Core 'B' Detector Circuit

Button
Function
S1601
Reset main microprocessor for
core B detector circuit
68
Siemens Industry, Inc.
Building Technologies Division
Condition
OFF
ON
1 flash every 2 seconds
2 fast flashes (every 2 seconds)
1 fast flash (every 1 second)
Flash (every 1 second) and 2 fast flashes
(every 2 seconds)
OFF
ON
1 flash every 2 seconds
2 fast flashes (every 2 seconds)
1 fast flash (every 1 second)
Flash (every 1 second) and 2 fast flashes
(every 2 seconds)
Position
Not pressed
Pressed
Position
Not pressed
Pressed
Position
Not pressed
Pressed
Definition
Default
Startup problems network core A (clock)
Failsafe active (no communication to the Operating
Unit)
Failsafe active + local alarm
Failsafe active + signaling (local alarm)
Failsafe active + local alarm + signaling
Default
Startup problems network core B (clock)
Failsafe active (no communication to the Operating
Unit)
Failsafe active + local alarm
Failsafe active + signaling (local alarm)
Failsafe active + local alarm + signaling
Definition
Normal
Resets only the main microprocessor on the periphery board
Definition
Normal
Resets only microprocessor on core A detector circuit
Definition
Normal
Resets only microprocessor on core B detector circuit
A6V10519176_enUS_b