Reset Procedures

Hard Reset
Soft Reset
Technical Manuals Online! - http://www.tech-man.com
There are two types of reset procedures that can be performed on the FireFinder-
XLS System: Hard Reset and Soft Reset.
Other terms for Hard Reset are Power-up, Initialization, and Cold Reset. Applying
power to the system performs a Hard Reset. Doing so initializes the whole system.
What Is Lost:
Alarm, supervisory, trouble, and security conditions (provided they have
returned to the normal state).
Arm/disarm.
Manual sensitivity adjustment.
What Is Not Lost:
Zeus program.
Time and date.
History log.
Time-based control.
A Soft Reset is performed by pressing the Reset System soft key. The system can
only be reset when all events (alarms, supervisories, securities and troubles) are
acknowledged and the notification appliances are silenced.
What Is Lost:
Alarm, supervisory, trouble, and security conditions (provided they have
returned to the normal state).
What Is Not Lost:
Any user entries such as time and date.
Arm/disarm.
Zeus program.
Manual sensitivity adjustment.
Time-based control.