Appendix; Function Block Lists - Samson TROVIS 5573 Mounting And Operating Instructions

Heating and district heating controller
Table of Contents

Advertisement

13 Appendix

13.1 Function block lists

CO1: HC1 · Heating circuit 1 (not system Anl 1.9)*
F
Function
01 Room sensor
RF1
02 Outdoor
sensor AF1
03 Return flow
sensor RüF1
04 Cooling control
05 Underfloor
heating
Drying of
jointless floors
06 Storage tank
sensor SF2
07 Optimization
08 Adaptation
EB 5573 EN
Comments
WE
Anl
Function block parameters: value range (default setting)
0
CO1 > F01 - 1: Temperature reading and FG1 input for
Not sys-
tems Anl
Types 5244 and 5257-5 or 5257-51 Room Panels active
1.5, 1.6,
3.x, 16.x
0
CO1 > F02 - 1: Outdoor-temperature-compensated control ac-
1.5, 1.6
tive
1
Not Anl
1.5, 1.6
0
1.2
CO1 > F03 - 1: Sensor and limitation function active
Function block parameters:
KP (limiting factor): 0.1 to 10.0 (1.0)
1
Not Anl
1.2
0
CO1 > F04 - 1: Cooling control, only with CO1 > F11 - 1
All*
The cooling control function causes a reversal of the operating
direction and a minimum limitation of the return flow tempera-
ture in HC1.
0
CO1 > F05 - 1: Restriction of the adjustment ranges
Not sys-
tems Anl
Function block parameters:
1.5, 1.6,
Start temperature: 20.0 to 60.0 °C (25 °C)
3.x, 16.x
Hold (days): 0 to 10 days (0)
Temp. rise/day: 0.0 to 10.0 °C (5.0 °C)
Maximum temperature: 25.0 to 60.0 °C (45.0 °C)
Hold (days): 0 to 10 days (4)
Temp. reduction/day: 0.0 to 10.0 °C (0.0 °C)
SToP,
CO1 > F06: Activate SF2 to switch off charging of the buffer
1
System Anl
16.x only
tank
0
CO1 > F07 - 1: only with CO1 > F01 - 1 and CO1 > F02 - 1
Not sys-
tems Anl
1.5, 1.6,
3.x, 16.x
0
Not sys-
CO1 > F08 - 1: only with CO1 > F01 - 1, CO1 > F02 - 1 and
tems Anl
CO1 > F11 - 0
1.5, 1.6,
3.x, 16.x
STArT,
STArT,
STArT,


Appendix
STArT

111