3.3 Changing parameters

Depending on the system code number selected and the activated functions, not all parame-
ters listed in the parameter list in the appendix (see section 13.2) might be accessible.
The parameters are grouped by topics:
− PA1:
HC1 (heating circuit 1)
− PA2:
HC2 (heating circuit 2)
− PA4:
DHW circuit
− PA5:
System-wide
− PA6:
Communication parameters
1. Turn the rotary switch to
Reading: 0 0 0 0
2. Enter valid key number [q].
3. Confirm key number [Û].
Reading: PA_
4. Select parameter level [q].
5. Open parameter level [Û].
6. Select parameter [q].
7. Activate editing mode for the parameter [Û].
blinks.
8. Change parameter [q].
9. Confirm parameter [Û].
Î To set further parameters in the opened parameter level, repeat the steps 6 to 9.
10. Select End [q].
11. Exit parameter level [Û].
Î To set further parameters in another parameter level, repeat the steps 4 to 9.
12. Turn the rotary switch back to normal switch setting
Note
All parameter settings are saved in a non-volatile memory in the controller.
26
(parameter and configuration level).
(information level).
EB 5573 EN