Mechanical installation
June 2019
Figure 3-9: Still Pipe Requirements
A. Max. 0.2 in. (5 mm)
B. Max. 1 in. (25 mm)
C. Min. 6 in. (150 mm)
D. Max. 1°
E. Level = 100%
F. Level = 0%
Chamber
Consider the following chamber requirements:
Pipes should be an all-metal material.
Pipe should have a constant inside diameter.
Inlet pipes should not protrude into the inside of the stand pipe.
The inner surface must be smooth and clear of any rough edges. (Smooth pipe joints
are acceptable, but may reduce accuracy.)
The gap between the cone antenna and the stand pipe should be maximum 0.2 in. (5
mm). If required, order a larger antenna and cut on location. See
antenna dimensions.
28
The gap between the cone antenna and the still pipe should be maximum
0.2 in. (5 mm). If required, order a larger antenna and cut on location. See
Table A-15
for antenna dimensions.
Reference Manual
00809-0300-4408
Table A-15
for
Reference Manual