Tank Shape - Emerson Rosemount 5408 Reference Manual

Level transmitter, non-contacting radar with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Configuration parameters
June 2019
Mounting type
Select option best describing how transmitter is mounted on the tank. There are four
options to choose from: Nozzle, Still pipe, Chamber, and Bracket.
The Bracket option should be used for measurements in open air installations such as
sumps or ponds, or when measuring through a plastic tank roof.
Figure C-5: Mounting Type
A. Nozzle
B. Still pipe
C. Chamber
D. Bracket (open air)
Inner diameter, pipe/chamber
Enter the inner diameter for the pipe or chamber in which the antenna is mounted. The
inner diameter value is used to compensate for the lower microwave propagation speed
inside the pipe/chamber. An incorrect value will give a scale factor error.

Tank shape

Select a tank shape that corresponds to the actual tank. If the actual tank does not match
one of the pre-defined tank shapes, then select Other (e.g. level measurements of sumps,
basins, or ponds).
Tank top shape
Form of the upper tank closure.
214
Reference Manual
00809-0300-4408
Reference Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents