Service and troubleshooting
June 2019
Table 7-11: Incorrect Level Readings
(1)
Symptom
Level is stuck in measuring range.
Level is stuck in full tank.
100
(continued)
Possible causes
Incorrect alignment of the
transmitter.
Disturbing objects in the
tank.
Time
Disturbing objects near the
antenna.
Time
Product build-up on the
antenna.
Cone antenna does not
extend below the nozzle.
Reference Manual
00809-0300-4408
Recommended actions
Verify the transmitter head is correctly
aligned, see
Align transmitter
Use the suppress false echoes function
to manage strong disturbance echoes,
see
Suppressing false
echoes.
Analyze the echo curve and check
amplitude thresholds, see
thresholds.
Remove the disturbing object.
Change alignment of transmitter head
in steps of about 15 degrees, see
transmitter
head. After each step,
check if impact of disturbing echoes is
decreased using the echo curve.
Put an inclined metal plate on top of
the disturbing object.
Move the transmitter to another
position. Refer to
Installation
considerations
for installation
considerations.
Use the suppress false echoes function
to manage strong disturbance echoes,
see
Suppressing false
echoes.
Analyze the echo curve and check
amplitude thresholds, see
thresholds.
For process seal antenna installed in a
nozzle taller than 10-in. (25 cm), adjust
the pre-configured amplitude
threshold, see
Handling disturbances at
top of
tank.
Increase the Upper Null Zone, see
Handling disturbances at top of
Remove the disturbing object.
Move the transmitter to another
position. Refer to
Installation
considerations
for installation
considerations.
Clean the antenna.
Use transmitter with air purging
connection.
Use the extended cone antenna.
head.
Amplitude
Align
Amplitude
tank.