Meaning Of The Parameters In The Parameterization Frame; Structure Of Parameterization Frame - Siemens SIMATIC S5 ET 200U Manual

Distributed i/o statio
Table of Contents

Advertisement

ET 200U(DP Standard): AddressAssignm.,Starting–Up, DiagnosingFaultsUsing COM ET 200
2. Enter the value in the "KH" format:

Structure of Parameterization Frame:

Figure 5-5 Structure of Parameterization Frame
The values of the bits in the parameterization frame are explained in the fol-
lowing table (default is always "0"):
Table 5-7

Meaning of the Parameters in the Parameterization Frame

Bit
Bit 0:
Result when pulling or plugging
in modules or when bus module
i
d l
h
b
d l
defective
Bit 1:
Evaluation of diagnostic data
from modules with diagnostics
f
d l
ith di
ti
capability
Bit 2:
Mode of the IM 318–C
Bit 3:
B d t
Baud rate of I/O bus
f I/O b
3. Confirm your input of the parameterization frame by pressing <F6>
5-16
Parameterization frame
7 6 5 4 3 2 1 0
0 0 0 0
Evaluation of diagnostic data from modules
Mode of IM 318–C
Baud rate of I/O bus
Value
0
All outputs are set to "0" in the case of a fault. The
ET 200U(DP Standard) station does not enter STOP mode.
1
The ET 200U(DP Standard) interrupts the "shifting" on
the I/O bus. The ET 200U(DP Standard) reads in the
plugged–in modules again and continues the data transfer
on the basis of the current values.
When "shifting" is interrupted, the output values are re-
tained.
0
Diagnostic data from modules with diagnostics capability
are not evaluated.
1
If modules with diagnostics capability are plugged–in, the
diagnostic data are evaluated.
0
IM 318–C acts as ET 200U(DP Standard), ET 200U(FMS)
or ET 200U in a mixed configuration.
1
IM 318–C is operated as combi slave.
0
The I/O bus is not operated in Slow Mode.
1
The I/O bus is operated in Slow Mode.
(ENTER).
Result when pulling or plugging–in modules
or when bus module defective
with diagnostics capability
Meaning
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b