Analog Input Module 464-8Ma21 - Siemens SIMATIC S5 ET 200U Manual

Distributed i/o statio
Table of Contents

Advertisement

Analog Value Processing
Table 7-10
Analog Input Module 464–8MA21, 4
tion (Bipolar); Thermoelement Type K (Nickel–Chromium/Nickel–Aluminium, according to IEC 584)
Units
Thermo
Tempera-
Voltage
ture in C
in mV*
>2359
1370
1369
54.773
1000
41.269
500
20.640
150
6.137
100
4.095
1
0.039
0
0
–1
–0.039
–100
–3.553
–101
–3.584
–150
–4.912
–200
–5.891
–201
–273
X
X
*
For a reference temperature of 0 C (32 F)
**
In the overrange, the current slope of the characteristic curve is maintained when leaving the linearized nominal range.
7-20
50 mV with Linearization and with Temperature Compensa-
High Byte
0 1 0 0 1 0 0 1 1 0 1 1 1 0 0 1
1370
0 0 1 0 1 0 1 0 1 1 0 1 0 0 0 1
1369
0 0 1 0 1 0 1 0 1 1 0 0 1 0 0 0
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
150
0 0 0 0 0 1 0 0 1 0 1 1 0 0 0 0
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
–101
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
–201
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0 1
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0 1
X X X X X X X X X X X X X 0 1 0
This value corresponds to the terminal temperature at wire break
Low Byte
Range
Overflow
Overrange**
Nominal Range
Accuracy
2 K
Overrange**
Overflow
Wire Break
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b