Programming An Acyclic Link (Msaz) - Siemens SIMATIC S5 ET 200U Manual

Distributed i/o statio
Table of Contents

Advertisement

ET 200U(DP Standard/FMS): Modes, Settings and Comm. Capabilities of IM 318–C

6.5.2 Programming an Acyclic Link (MSAZ)

The example describes the configuration of the FMS service "Identify" in an
acyclic link.
Prerequisite: You have started SINEC NCM and are now in the selection
screen.
You have completed the "Init – Edit start screen" and the "Edit – CP Init ba-
sic initialisation" screens.
1. Enter the relevant values in the "CP link programming" screen in order to
CP Link Programming
Communication reference:
LOCAL PROGRAMMING
PLC details
SSNR:
0
ANR:
1
ANZW:
MW 100
PRIO:
LOW
Local LSAP:
REMOTE PROGRAMMING
Remote LSAP:
Password:
Access to variables:
F
F
F
1
2
3
+ 1
– 1
Figure 6-6 "CP Link Programming" Screen
2. Confirm your inputs by means of <F7> (OK).
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
configure an acyclic link.
Enter "26" in the "Remote LSAP" input field for an acyclic link (
6-37, Section 6.3.3); enter the station number of the ET 200U(FMS) in
the "Remote L2 address" input field.
2
Type of link:
Monitoring interval:
58
Max. PDU length:
26
Remote L2 address:
F
F
4
5
INPUT
Result: You have now completed the configuring procedure.
SINEC NCM