Parameters

2.1
Parameters
Table 2-1
Parameters for analog output module
2AO I ST
Group diagnostics (parameter
assignment error, internal
error)
Diagnostics: Wire break
Response to CPU/master
STOP
Type/range of output
Substitute value
2
No diagnostics detection between -1.1852 mA and +1.1852 mA.
1
If there is no voltage being supplied to the interface module or COMPACT module but the supply to the analog output
2
modules continues, the substitute values that have been assigned parameters are output. Substitute values must be within
the nominal range. You can assign values from -27,648 to +27,648 as parameters (when assigning parameters using the
GSD file).
2AO I ST analog electronic module (6ES7135-4GB01-0AB0)
Manual, 04/2007, A5E01076949-01
Range of values
Disable
Enable
Disable
1
Enable
No output current or voltage
Substitute a value
Keep last value
Deactivated
4 to 20 mA
± 20 mA
To 65,535 (value range must lie
within the nominal range)
Default setting
Disable
Disable
No output current or voltage Module
4 to 20 mA
± 20 mA: 0 mA
4 to 20 mA 4 mA
2