Structure Of The Diagnostics Word After Request Of The Station Status; Structure Of The Diagnost. Word After Request Of The Station Status - Siemens SIMATIC S5 ET 200U Manual

Distributed i/o statio
Table of Contents

Advertisement

ET 200U(DP Standard): AddressAssignm.,Starting–Up, DiagnosingFaultsUsing COM ET 200
Diagnostics Word "Station status 1 and station status 2", code = 0
Diagnostics address
"Station status 1"
7 6 5 4 3 2
1 0
1: The configuration data sent from the master to the slave station do not corre–
1: Station diagnostics or module diagnostics are in operation.
1: Function is not supported.
0: Bit is always "0".
1: Slave station is not an ET 200U (parameter assignment error).
1: Slave station has been parameterized from another master.
Figure 5-12 Structure of the Diagnostics Word after Request of the Station Status (Station Status 1 and Station
Status 2)
Diagnostics Word "Station status 3 and master address", code = 1
Diagnostics address
"Station status 3"
7 6 5 4
3 2 1 0
Irrelevant
Figure 5-13 Structure of the Diagnost. Word after Request of the Station Status (Station Status 3 and Master Address)
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Diagnostics address + 1
"Station status 2"
7 6 5 4 3 2 1 0
1: Slave station cannot continue operation if
1: Bit is always "1".
1: Response monitoring has been activated.
1: Slave station is in FREEZE mode.
1: Slave station is in SYNC mode.
0: Bit is always "0".
1: Slave station is deactivated.
1: Slave station cannot be accessed.
1: Slave station is not yet ready for data exchange.
spond with the structure of the slave station.
Diagnostics address + 1
"Master address"
7 6 5 4 3 2 1 0
Address of master which has
parameterized the slave station
1: Slave must be reparameterized.
the fault has not been remedied.
5-35