Diagnostics Data" Object - Siemens SIMATIC S5 ET 200U Manual

Distributed i/o statio
Table of Contents

Advertisement

ET 200U(DP Standard/FMS): Modes, Settings and Comm. Capabilities of IM 318–C
Diagnostics Data
The "diagnostics data" object contains the diagnostics messages of the
ET 200U(DP Standard/FMS). The FMS master can read the "diagnostics
data" object.
The following tables show the structure of the "diagnostics data" object and
the diagnostics messages, respectively.
Table 6-13
INDEX:
OBJECT_CODE:
DATA_TYPE_INDEX:
LENGTH:
LOCAL ADDRESS:
PASSWORD:
ACCESS_GROUPS:
ACCESS_RIGHTS:
NAME[16]:
EXTENSION_LENGTH:
The length of the diagnostics messages is 13 octets:
Table 6-14
The following tables describe the meanings of the various diagnostics mes-
sages:
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b

"Diagnostics Data" Object

Structure of the Diagnostics Messages of the ET 200U(DP Standard/
FMS)
Octet
1
Station status 1
2
Station status 2
3
Station status 3
4
DP master address
5
Manufacturer identification (I)
6
Manufacturer identification (II)
7
Header (station diagnostics)
8
Station diagnostics
9
Header (module diagnostics)
10
Module diagnostics (slots 0 to 7)
11
Module diagnostics (slots 8 to 15)
12
Module diagnostics (slots 16 to 23)
13
Module diagnostics (slots 24 to 31)
110
7 (Simple–Variable)
10 (Octet string)
13
R
Diagnostics data
0
Diagnostics Message
6-19

Advertisement