Correction Procedures; Rebooting The Software; Restoring Factory Settings - ABB Relion 615 Series Operation Manual

Ansi
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MAC054853-MB B
7.3
7.3.1
7.3.2
615 series ANSI
Operation Manual
Warning indication
Warning code
Warning
ARC3 cont. light
Warning
RTD card error,X130
Warning
RTD meas. error,X130

Correction procedures

Rebooting the software

1.
Select Main menu/Configuration/General/Software reset and press
2.
Change the value with

Restoring factory settings

In case of configuration data loss or any other file system error that prevents the protection
relay from working properly, the whole file system can be restored to the original factory
state. All default settings and configuration files stored in the factory are restored. Only
the administrator can restore the factory settings.
1.
Select Main menu/Configuration/General/Factory setting and press
2.
Set the value with
3.
Confirm by selecting Yes with
The protection relay restores the factory settings and restarts. Restoring takes 1...3
minutes. Confirmation of restoring the factory settings is shown on the display a few
seconds, after which the relay restarts.
Avoid the unnecessary restoring of factory settings, because all the
parameter settings that are written earlier to the relay will be overwritten
with the default values. During normal use, a sudden change of the
settings can cause a protection function to trip.
To restore factory settings from bootloader mode, press ESC + KEY
simultaneously for 5 seconds.
Additional information
87
A continuous light has been detected on
the ARC light input 3.
96
Temporary error occurred in RTD card
located in slot X130.
106
Measurement error in RTD card located in
slot X130.
or
and press
or
and press
.
or
and press
Section 7
Troubleshooting
.
.
.
.
115