Warnings - ABB Relion 615 Series Operation Manual

Ansi
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MAC054853-MB B
7.2.2
615 series ANSI
Operation Manual
Fault indication
Internal Fault
FPGA error
Internal Fault
RTC error
Internal Fault
RTD card error,X130
Internal Fault
COM card error

Warnings

Warnings are indicated with the text Warning additionally provided with the name of the
warning, a numeric code and the date and time on the LHMI. The warning indication
message can be manually cleared.
If a warning appears, record the name and code so that it can be provided
to ABB customer service.
A071222-ANSI V1 EN
Figure 81:
Warning
Fault code
Additional information
83
Error in the FPGA on the CPU card.
84
Error in the RTC on the CPU card.
96
RTD card located in slot X130 may have
permanent fault. Temporary error has
occurred too many times within a short
time.
116
Error in the COM card.
Section 7
Troubleshooting
113

Advertisement

Table of Contents
loading

Table of Contents