Section 6
Operating procedures
6.1.3.1
6.1.3.2
94
DFR records
Fault records
Events
Load profile record

Creating digital fault records

Normally DFR recordings are triggered by the protection relay applications but the
recording can also be triggered manually.
1.
Select Main menu/DFR records.
2.
Select Trig recording with
3.
Press
, change the value with
A070861-ANSI V2 EN
Figure 62:
Changing the value
The DFR recorder is now triggered.

Monitoring DFR data

Upload individual disturbance recordings from the protection relay with the PCM600
software to monitor DFR data.
1.
Select Main menu/DFR records.
All the DFR information is listed.
2.
Scroll the view with
The following items are listed in the view:
or
.
or
and press
or
.
1MAC054853-MB B
again.
615 series ANSI
Operation Manual