Correction Procedures; Rebooting The Software - ABB REX610 Operation Manual

Hide thumbs Also See for REX610:
Table of Contents

Advertisement

2NGA000823 A
7.3
7.3.1
REX610
Operation Manual
Warning indication
Report cont. Error
SCL config error
Logic warning
SMT connect error
GOOSE input warning
ACT Config. mismatch
SDcard mount Warn
PSU.data.invalid
DIO.data.invalid
AIU.data.invalid
AIC.data.invalid
HMI.data.invalid
LHMI keyscan error
GOOSE receive error
GOOSE publish error
SDcard memory full
Device Cert. Expired
SDcard error
SNTP error
Internal voltage error
Inter. humidity sensor error
Inter. temp. sensor error
Access Errx
Config. not available
SCL validation warning
MMS report warning
MMS service warning
1) Used for software simulation

Correction procedures

Rebooting the software

1.
Select Main menu/Configuration/General/Software reset and press
2.
Change the value with
Warning category
Additional information
IEC report error
1)
25
27
Error in SCL configuration file or the
file is missing
28
Too many connections in the
configuration
29
Error in SMT connections
Error in GOOSE connections
30
1)
37
Configuration mismatch
156
SD card mount error
PSU traceability warning
1)
160
DIO traceability warning
1)
161
AIU traceability warning
1)
162
AIC traceability warning
1)
163
HMI traceability warning
1)
164
Keyscan error
1)
169
170
Error in GOOSE message receiving
Error in GOOSE publish
1)
171
172
SD card memory is full
173
Device certificate expired
174
Error in SD card
175
Error in the SNTP module
Voltage error detected
1)
176
177
Error in internal humidity sensor
178
Error in internal temperature sensor
179
Setting write failure
181
Error in ACT connections/ACT
Configuration not available
182
Failure in SCL file validation
MMS report warning
183
1)
MMS service warning
1)
184
or
and press
.
Section 7
Troubleshooting
.
63

Advertisement

Table of Contents
loading