Correction Procedures; Rebooting The Software; Restoring Factory Settings - ABB RELION 620 Series Operation Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC456939-IB D
7.3
7.3.1
7.3.2
620 series ANSI
Operation Manual
Warning indication
Warning code
Warning
GOOSE Rx. error
Warning
AFL error
Warning
Unack card comp.
Warning
Protection comm.
Warning
ARC1 cont. light
Warning
ARC2 cont. light
Warning
ARC3 cont. light
Warning
RTD card error,X105
Warning
RTD card error,X110
Warning
RTD card error,X130
Warning
RTD measurement error
in X105
Warning
RTD measurement error
in X110
Warning
RTD meas. error,X130

Correction procedures

Rebooting the software

1.
Select Main menu/Configuration/General/Software reset and press
2.
Change the value with

Restoring factory settings

In case of configuration data loss or any other file system error that prevents the protection
relay from working properly, the whole file system can be restored to the original factory
state. All default settings and configuration files stored in the factory are restored.
Additional information
32
Error in the GOOSE message receiving
33
Analog channel configuration error
40
A new composition has not been
acknowledged/accepted.
50
Error in protection communication
85
A continuous light has been detected on
the ARC light input 1.
86
A continuous light has been detected on
the ARC light input 2.
87
A continuous light has been detected on
the ARC light input 3.
90
Temporary error occurred in RTD card
located in slot X105
94
Temporary error occurred in RTD card
located in slot X110
96
Temporary error occurred in RTD card
located in slot X130.
100
Measurement error in RTD card located in
slot X105
104
Measurement error in RTD card located in
slot X110
106
Measurement error in RTD card located in
slot X130
or
and press
.
Section 7
Troubleshooting
.
107